An acrylic based firestop sealant that provides movement capability in fire rated joints and seals through-penetrations applications.
Chemical basis | Water-based acrylic dispersion |
Color | Available in red, white and gray |
Density | 99.9 lb/ft³ |
Application temperature | 35°F to 104°F (1.5°C to 40°C) |
Storage temperature | 35°F to 95°F (1.5°C to 35°C) |
Temperature resistance | -22°F to 176°F (-30°C to 80°C) |
Shelf life | 24 months |
Tack free time | 23mins (ventilated at 77°F, 80% rel. humidity) |
Skin-forming time | Approx. 15 min |
Curing time | Approx. 3 mm / 3 days |
Average volume shrinkage (ASTM C1241) | 22% |
Movement capability | Up to 33% |
Mold & mildew | Class 0 (ASTM G21-96) |
Electrical resistance | Yes |
LEED Compliant | Yes (CDPH v1.2-2017) |
LEED VOC | 63 g/L |
Intumescent | No |
Seismic resistant | Yes |
Water tightness | Yes |
Temperature resistance | -22°F to 176°F (-30°C to 80°C) |
Surface burning characteristics (ASTM E 84-96) |
Flame Spread: 10 Smoke Development: 0 |
Surface burning characteristics (CAN/ULC-S102) |
Flame Spread: 14 Smoke Developed: 4 |
California State Fire Marshall Approvals | Yes (pens & joints) |
City of New York approval | Yes (CP606 MEA 100-99-MV6) |
Air leakage (UL 2079 L-Rating) | L-Rating at Ambient = Less than 1 CFM / Lin Ft. L-Rating at 400%F = Less than 1 CFM / Lin Ft. |
Sound transmission classification (ASTM E 90-99) |
56 (Relates to specific construction) |
Tested in accordance with |
UL 2079, ASTM E 814, ASTM E 1966, ASTM E 2837, UL 1479, ASTM G21, ASTM C1241, CAN/ULC-S115 |
• Various base materials such as masonry, concrete, gypsum, etc.
• Wall and floor assemblies rated up to 3 hours• Where a gypsum wall assembly meets the underside of a metal or concrete deck
• Sealing expansion joints to impede the passage of fire, smoke and toxic fumes• See Hilti literature or third-party listings for complete application and installation details